Optically isolates and converts unbalanced half- or full-duplex RS-232 signals to optically isolated and balanced full-duplex RS-422 or 2-wire half- or 4-wire full-duplex RS-485.
Switch-selectable data rates between 2400 bps and 19.2 kbps.
Conveniently mounts on a DIN rail.
Power up to six of the converters with our optional DIN Rail 12-VDC Power Supply (PSD100).
Warranty: 1 Year Double Diamond™ Warranty (Standard)
Optically isolates and converts unbalanced half- or full-duplex RS-232 signals to optically isolated and balanced full-duplex RS-422 or 2-wire half- or 4-wire full-duplex RS-485.
Switch-selectable data rates between 2400 bps and 19.2 kbps.
Power up to six of the converters with our optional DIN Rail 12-VDC Power Supply (PSD100).
Distance (Maximum) — 1219.2-m Isolation — 2000 VAC optical isolation of data signals and ground Operating Temperature — -40 to +80° C Operating Humidity — Up to 95% noncondensing Operation — RS-232: Half- or full-duplex; RS-485: 2-wire half-duplex or 4-wire full-duplex; RS-422: Full-duplex
Speed — 2400 bps to 19.2 kbps, switch-selectable; other rates available between 1200 bps and 115.2 kbps Surge Suppression
- Bidirectional avalanche breakdown device: 7.5 V; Peak power dissipation: 500 W; Clamping time: <1 psec Connectors — (2) 6-position terminal blocks, (1) DB9 F (DCE) Indicators — (3) LEDs: (1) RS-485 transmit data, (1) RS-485 receive data, (1) power Power
- 10–30 VDC, 100 mA Dimensions — 2.5(H) x 7.9(W) x 10.7(D) cm
Datasheets
RS-232 to RS-422/RS-485 DIN Rail Converter with Opto-Isolation Datasheet